Specification Rating/Description Condition
Supported
Interfaces
standard models: GPIB and RS 232 Support SCPI command set for GPIB and RS 232 (see KLP Developer's Guide)
E-Series models: GPIB and LAN
Support four interfaces for LAN:
   1. Web interface, port 80
   2. SCPI Telnet, port 5024
   3. SCPI Sockets, port 5025
   4. VXI 11, port 1024
Support SCPI command set for GPIB and LAN; (see KLP Developer's Guide)
GPIB GPIB address range: 1 to 30 Factory default is 6.
RS 232 standard models only: Baud Rate range: 2400, 4800, 9600, 19,200 or 38,400 Factory default is 38,400.
Digital remote
control
isolation: Safety Extra Low Voltage (SELV)  
format: compatible with SCPI protocols W98 SE and later operating systems.
Programming resolution 0.024% of Emax and Imax  
Programming accuracy 0.05% of Emax and Imax  
Readback resolution 0.024% of Emax and Imax  
Readback accuracy Either 0.1% of Emax and Imax or front panel voltmeter or ammeter display resolution, whichever is greater. (1) ±1 LSB
Status reporting OVP, OCP, OTP, output lead fault (OLF), fan failure,
power loss
Detected fault shuts down power supply output. Overvoltage and overcurrent protection values can be individually proogrammed.
NOTES:
(1) Display resolution is determined by the number of significant digits shown, relative to the decimal point. Resolution is 10-X where X is the number of digits to the right of the decimal point. E.g., for display of 10.00V, resolution is 10-2 or 0.01 or 10mV; for display of 150.0A, resolution is 10-1 or 0.1 or 100mA.